HVM Test Reports: What Specifiers Should Check Before Approval

A performance rating can fit neatly into a specification while the tested product does not fit the project. An HVM test report review is therefore essential before a bollard, blocker or gate is approved—not after procurement has started.

Confirm exactly what was tested

Start with product identity. Check the manufacturer, model, designation and tested configuration: number of units, spacing, overall length, barrier height, anchorage, fixings, foundation and ground conditions. For an active barrier, confirm that the tested assembly matches the proposed operating system.

Then verify the impact conditions. The report should identify the standard and edition, test vehicle, actual mass, impact speed, angle and impact location. ISO 22343-1:2023 establishes the vehicle-impact test method and performance rating, while ASTM lists F2656/F2656M-23 as its active crash-testing method.

Read beyond the headline rating

A useful HVM test report review checks vehicle penetration, major debris distance and the final condition of the barrier, vehicle and foundation. Photographs and video help explain deformation, component separation and the actual impact point. The result should also be traced to the test house and its scope of accreditation.

NPSA’s 2025 due-diligence advice recommends requesting the independent test report, reviewing test-house footage and confirming that the tested performance meets the project’s Operational Requirement.

Compare evidence with the real installation

The final step is comparison. Differences in geometry, foundations, soil restraint or interfaces may change the impact load path. GloBAS Engineering’s FEA, dynamic analysis and design optimisation services can help assess those differences and identify where further verification is needed.

Before approving a barrier, make the HVM test report review part of the technical submittal. The rating is the summary; the full evidence determines whether it applies.

Last news

Our Events

Dear Visitor,

Thank you for your interest. The form has been successfully send and we will get back to you within 1 working day.

Looking forward to further communication,

With the best regards,

GloBAS Engineering Team

UAE, Dubai, P.O.Box 43585

Phone: +971 056 240 6055

voronkina@globasgroup.com

REQUEST

Please, fill in the form below.

By leaving a request, you agree to the personal data processing policy